8.1 Set the fan cycling ON time and OFF time.
a. Press and hold the Select button until “LI” or ”UnLI” or ”CALC” appears on display.
b. Using the “+” and “-“ buttons select between:
“LI” – Fan cycling limited - default.
If “LI” is selected – no need to set “Fd” (Fan duty cycle) and “Ft” (Total
period).
“UnLI” – Fan cycling unlimited ON time.
Fan will be energized continuously after no fan activity for the fan OFF time.
“CALC” – Fan cycling calculated.
Fan cycling times will be calculated based on the fan duty cycle (“Fd”) and
total period (“Ft”).
If “CALC” is selected – go directly to 8.2 – no need to set “FO” (Fan cycling
limited ON time), “FF” (Fan cycling limited OFF time), “dO” (Damper cycling
OPEN time”) and “dC” (Damper cycling CLOSED time).